Safety Warning: Refrigerant handling requires professional certification. Unplug the unit and discharge capacitors before starting.
Tools Needed: Brazing torch, vacuum pump, refrigerant recovery machine, replacement compressor, new filter drier.
- Recover existing refrigerant using a certified recovery machine.
- Disconnect the electrical harness and suction/discharge lines from the old compressor.
- Remove the mounting bolts and extract the compressor.
- Install the new compressor and secure the mounting bolts.
- Braze the suction and discharge lines, ensuring a leak-proof seal.
- Install a new filter drier to ensure system cleanliness.
- Evacuate the system to a deep vacuum and recharge with the specific refrigerant amount indicated on the unit's nameplate.
- Power on the unit and verify that the compressor runs smoothly without grinding noises.